Eaton Logo

How do I fix an F36 Compatibility Fault code for a DG1 drive?

The compatibility fault is due to the power board not matching the control board, if the control processor is not able to read the correct control type code and EEPROM codes that are set in the factory the drive will go into fault. This could be an issue with the software loading, perform a factory reset and see if the fault will clear. If a factory reset does not work, reload software to the control board and see if fault clears, if fault does not clear need to replace control section.