I cannot copy programming between an 9000X AF drive and an HVX9000 AF drive. It says fail then SVCHST-05

When copying and pasting using the keypad on the 9000X series VFDs (including the SPX9000, SVX9000, HVX9000) the application(s) in the drive needs to be present or match.  HVX9000 programming removes the standard SVX and SPX application files when loaded so you cannot copy over a parameter set to the drive if the application file does not exist.  Example - SVX contains Standard application (amongst others) when copying to another drive even if it has a different application selected you can still load that parameter set.