Eaton Logo

Can A class T fuse be used in place of the published J class fuse for XTCE contactors as it relates to SCCR ratings

Yes, a Class T can be substituted for a Class J, as they have the same let-thru umbrella properties.This would be acceptable

 

I need the SCCR, short circuit current ratings for Electrical Componants