Are Quicklag cable-in/cable-out, plug-on, and bolt-on miniature circuit breakers suitable for use at 400 Hz?

The standard Quicklags such as QC, HQP, and BAB breakers are not rated for 400 Hz operation. To order a Quicklag breaker suitable for use at 400 Hz, add modification code G to the end of the circuit breaker catalog number.

EXAMPLE: BAB3100HG or QC1020G.

NOTE: The IC rating is reduced to .2 of the standard IC rating.