What trip curves are available for the FAZ UL489 breakers?

The trip curves are as follows:

FAZ-NA---B curve which means 3-5X current rating. B-curve devices are suitable for applications where low levels of inrush current are expected

FAZ-NA--C curve which means 5-10X current rating. C-curve devices are suitable for applications where medium levels of inrush current are expected. (examples: small transformers, lighting, pilot devices, control circuits and coils).

FAZ-NA--D curve which means 10-20X current rating. D-curve devices are suitable for applications where high levels of inrush current are expected.