What is the magnetic trip range for a KD breaker?

The minimum magnetic trip range for the KD Frame breaker would be 5X the thermal. The magnetic trip range for the KD Frame breaker would be between 5 times and 10 times the thermal amps. All settings are discrete. To determine the increments between, reference Breaker Dial Settings from the attached file.

  1. MoldedCaseDialSettings_MD08703005E.PDF