What options do I have for unused outputs on my C445 Motor Management Relay?

The Operation mode for a C445 determines which outputs are available for other purposes. For example, if the operation mode is Direct (FVNR), then only Output 1 (Q1) is assigned for use by that operation mode. Q2 and Q3 are available for other purposes. By default, they are general purpose outputs that can be controlled via a communication network. By using either the Power Xpert inControl software or the Monitoring User Interface (MUI), many other options may be assigned to these outputs, including specific or general fault or warnings as well as running status.