For a C441 Motor Insight application on Ethernet with a C441 Ethernet module, if periodic communication losses occurs for known reasons, how can the device be configured to not require a reset?

By default, C441 Ethernet modules require a reset following a communication loss. Setting parameter 106 on the web pages for the device from a default value of 1 to a value of 2 will allow the module to auto recover from a communication loss, thereby resetting the fault and begin communicating again when communications is re-established by the master. If a communication loss occurs, this will not prevent the C441 from tripping the motor. It will just allow it to auto recover when communications is recovered.