When using the Voltage Loss Restart feature with the C445 Motor Management relay, does control power need to be maintained when the 3-phase voltage drops below the Voltage Loss Restart Loss Level?

Yes, a separate source such as a UPS must be used to maintain control power to the C445 for the Voltage Loss Restart feature to function.