Eaton Logo

What is the replacement feeder group part number for Freedom size 6 contactors/starters?

The feeder group voltage must match the coil voltage. The size 6 starters have a coil feeder group that supplies power to the operating coil. If the coil is changed to a different voltage the feeder group must also be changed.
 
VoltageFeeder group
120V60Hz/110V50Hz
9-3007
240V60Hz/220V50Hz9-3007-2
480V60Hz/440V50Hz9-3007-3
600V60Hz/550V50Hz9-3007-4
380–415V50Hz9-3007-8
24V60Hz/50Hz9-3007-7
48V60Hz9-3007-9