Where do I set the dial on a Freedom C306 overload for 1.15 service factor motor?

For motors having a 1.15 service factor or larger, rotate the FLA (Full Load Amperes) adjustment dial to correspond to the motor’s FLA rating. Estimate the dial position when the motor FLA falls between two letter values. For motors having a 1.0 service factor, rotate the FLA dial one-half position counterclockwise (CCW). More information on this and example diagrams can be found in volume 5 tab 2 of the online catalog.
 
 http://www.eaton.com/Eaton/ProductsServices/Electrical/Support/Documentation/Catalogs/Volume5/index.htm