Eaton Logo

What is the contact resistance for the V201 vacuum Size 4 contactors?

The typical resistance values are:

  • A new VI
    • Average --- 53
    • Maximum --- 100  micro-ohms
  • A VI after arcing
    • Average --- 120 micro-ohms
    • Maximum --- 200  micro-ohms