S811+ stop from the DIM

When the S811+ is being operated via a (Modbus) network, the unit will recognize a STOP command from the Stop button on the Digital Interface Module (DIM). The S811+  will stop in accordance with the appropriate parameter settings. This action will also place the unit into Hand mode at the same time. To issue a RUN command from the network after pressing the Stop button on the DIM, the S811+ is required to be again placed in the Auto mode.

 

NOTE: When controlling the S811+ from a Modbus network and the Stop button is pressed, the Local bit is set in the Status word so the PLC will be able to recognize that the S811+ is in Local following this action.