FC46 on an S811+

Fault Code 46 (FC46) is an unpublished fault code that did not get listed in the S811+ user manual in time for publication.

This is a communication fault between two processors on the printed circuit board (pcb), requiring replacement of the pcb.

Typically, this fault cannot be reset and the unit does not fun.