A200 300/5 rationCurrent transformer data.

The A200 starter CT,. part number 655C285H03 meets USASI Spec No C57-13-1968

The CT meets the following classe and burden

0.3 B0.5  = 12.5VA

0.3 B0.2  = 5VA

0.3 B0.1 =  2.5VA

 

At 100% of rated load, correction factor is between 0.994 and 1.012. At 10% of rated load current, correction factor is between 0.976 and 1.024.