Eaton Logo

Why can't I clear an Internal Comms fault on the S811+?

This fault indicates that there is a communications issue between the mother board and the daughter board on the printed circuit board. Experience has shown that this condition cannot be corrected in the field by cycling 24 Vdc control power. Printed circuit board replacement is required to correct this condition.