Eaton Logo

Looking for a 30amp normally closed DP contactor ?

All of the C25 definite purpose contactors have normally open power poles - they do not come in normally closed power poles.  We do have the C30CNE lighting contactor which is rated 30amps per pole and can have normally open OR normally closed power poles.  It can be used on non-lighting applications.  Also we have a DPDT control relay, the 9575H series that can be used for a 2pole Normally Closed application up to 40amps up to 300Vac or below.

Lighting Contactor Selection for the C30CNE

The 9575H relays are in Volume 7 tab 3 page 118. Link below.

http://www.eaton.com/Eaton/ProductsServices/Electrical/Support/Documentation/Catalogs/Volume7/index.htm

Eaton Logo