M-Max (MMX) PID Control - Keypad Setpoint - AI1/AI2 Transducer
PID Control - Keypad Setpoint - AI1/AI2 Transducer Reference:
See table below, program these values first. Then follow the steps below after that to complete the setup.
Parameter |
Designation |
Basic [0] |
Pump [1] |
Fan [2] |
High Load [3] |
P1.1 |
Quick Start Parameters |
0 |
0 |
0 |
0 |
P1.2 |
Application |
0 |
1 |
2 |
3 |
P6.3 |
Minimum Frequency [Hz] |
00.00Hz |
20.00Hz |
20.00Hz |
00.00Hz |
P6.4 |
Maximum Frequency [Hz] |
60.00Hz |
60.00Hz |
60.00Hz |
60.00Hz |
P6.5 |
Accel. Time 1 [sec] |
10.0s |
15.0s |
20.0s |
5.0s |
P6.6 |
Decel. Time 1 [sec] |
10.0s |
15.0s |
20.0s |
5.0s |
P6.7 |
Start Function |
0/Ramp |
0/Ramp |
0/Ramp |
0/Ramp |
P6.8 |
Stop Function |
0/Coast |
1/Ramp |
0/Coast |
0/Coast |
P7.1 |
Motor Rated Current [Amps] |
NP |
NP |
NP |
NP |
P7.2 |
Current Limit [Amps] |
** |
** |
** |
** |
P7.3 |
Motor Rated Speed [RPM] |
NP |
NP |
NP |
NP |
P7.4 |
Motor Power Factor [0 ≤ P.F. ≤1] |
NP |
NP |
NP |
NP |
P7.5 |
Motor Voltage [VRMS] |
NP |
NP |
NP |
NP |
P7.6 |
Motor Rated Freq. [Hz] |
NP |
NP |
NP |
NP
|
Note: Drive will run motor when transducer signal is below setpoint |
The following parameters must be changed after completing the Standard Parameters table
- P9.1 PID Controller = 1 [Activated]
- P9.4 PID Controller Setpoint, keypad = Setpoint [%]
- P9.6 PID Controller Process Variable (Transducer Feedback) = 1 (AI1) or 2 (AI2)
- P9.9 PID Controller Inversion Control = 0 (Not Inverted)
- P9.12 Sleep Mode Frequency = USER DEFINED [Hz]
- This value CANNOT be the same as the P6.3 Minimum Frequency, needs to be different (i.e. min freq. = 20.00 Hz, Sleep Mode Freq = 20.01 Hz)
- P9.13 Sleep Mode Wake Up Point = USER DEFINED BELOW SETPOINT [%]
- P9.14 Sleep Mode Delay Time = USER DEFINED [sec]
- Set Drive to I/O control by pressing the LOC/REM button, check the arrow indicator.
- Drive will start/stop by the I/O Terminal, DI1 (PIN 8) will need to have 24VDC applied.
- Drive will run PID algorithm when start signal is applied. When output frequency drops below Sleep Mode Freq., the drive will stop running, until Wake-Up point is reached by going below Setpoint [%].