Eaton Logo

HMX (H-Max) F32 Fan Life Time Counter Reset

If HMX (H-MAX) drive is getting a F32 Fan Life Time Warning, this means that the fan life time counter has reached 10,000 hours of operation. The counter can be reset by using P4.6.1.7 Fan Lifetime Reset Counter. Use this to reset the F32 Fan Alarm.  To get to the Main Menu, press and hold the LEFT arrow on the keypad. Navigate down to I/O Hardware then Power Unit Settings and finally Fan Control. The parameter to reset the fan counter is towards the bottom of this menu page.

Use the OK button to enter menus and left arrow to back out to previous menu. 

Eaton Logo