How do I fix an F37 Device Change Fault code for a DG1 drive?

Device change fault occurs when different option card or control board is installed. This fault is looking at the serial numbers stored in the EEPROM on the circuit boards and if it has one registered and after adding a different circuit board it would change. This fault comes from the control board. When this fault occurs a power cycle should clear the fault.