Eaton Logo

Do the FAZ D-Curve Breakers Have Similar Characteristics as a PD1?

Yes, the FAZ D-trip characteristic is 10x to 20x the current rating of the breaker and a PD1 breaker, 3 pole, the trip range magnetically is 11x to 19x the current rating of the breaker, so these are in fact similar.