Does the C441 have a "READY" status output signal?

By itself, the C441 does not have a dedicated output to indicate the unit is able to achieve Ready status after an overload (OL) trip. 

If the unit is connected to a network, Modbus address 314 can be monitored. A trigger can be set to inform a user when the thermal capacity (TC) is below 99%, or any other setpoint to indicate the unit is able to be reset and restarted.